| ACCESSORIES: |
|
|
| |
|
|
|
| |
|
|
|
| SELECTION
REMINDERS: |
|
|
| |
|
|
|
| 1. |
Standard
ratings for:
15/25/35 kV |
2. |
The
standard splice is equipped
with protective covers and a |
|
Voltage:
to 25 kV, |
|
mounting
bracket. |
|
Impulse
Voltage: to 125 kV BIL |
|
|
|
Corona Extinction:
to 19 kV |
3. |
Many
combinations of 200/600/900 |
|
Standard ratings for 35 kV Y
|
|
Amp junction
bars are available. |
|
Splice: |
|
|
|
Voltage:
35 kV
Impulse Voltage: 150 kV BIL
Corona Extinction: 26 kV |
|
|
|
|
|
|
| ORDERING
PROCEDURE: |
|
|
|
|
|
|
| 1. |
Determine
the following: |
|
Example
1: |
| a. |
Maximum voltage, kV. |
|
25 kV (corona
extinction = 19 |
| b. |
Current Rating, Amp. |
|
kV) |
| c. |
Number
of positions required for |
|
3-200 Amp
universal bushing |
| |
installation |
|
wells required straight
inline |
| d. |
Configuration
of splice |
|
and 6-600A
standard bushings |
| |
|
|
required
at 90 deg
with single |
| 2. |
Select
single casting 3 phase |
|
casting |
| |
device
or 3 x 1 single phase |
|
Catalog Number JBY-3A/6B-19 |
| |
devices
on common frame |
|
|
|
|
|
Example
2: |
| 3. |
Select catalog
number of splice |
|
Same as above
but with 3 x 1 |
|
|
|
single phase |
| |
|
|
|
| 4. |
Provide
the maximum voltage, kV |
|
Catalog Number JBY3-1A/2B-19
|
|
and substitute
its corresponding corona extinction value for x
in
the catalog number. |
|
|
|
|
|
|