high voltage cable couplers, junction bars, trailing cable coupler, design and manufacturing, ship to shore power, cold ironing, trolley shoes, substation, cable bracket, bus support, capnut termination, cable transitions, ground fault protection, PILC Cable, aircraft warning marker, oil stop module, mining products, utility products, patton, cooke


mining products utility products transportation products tunnel boring machines & shore power Patton & Cooke Company
home
products
brochures
case studies
multimedia
contact us
utility > products > junction bars > l splice


L Splice Junction Bars


            

Patton & Cooke Co's L Splice Junction Bar accommodates cable connections where space restrictions limit the ability to bend cable. It provides rigid connections for special switching applications. Available in a multitude of configurations rated up to 25kV.

L Splice Catalog Numbers

15 / 25 kV
Illustration
(not to scale)
Desc   P & C
Cat No
Dimensions Weight
Length Width Height
mm in mm in mm in kg lb

JBL-2A1A-19

3 Point
1 Phase
2 x 200 A
1 x 200 A

JBL-2A/1A-19 330 13.00 121 4.75 121 4.75 7 14

JBL-4A2B-19

6 Point
1 Phase
4 x 200 A
2 x 600 A

JBL-4A/2B-19 441 17.38 257 10.13 146 5.75 12 26
ACCESSORIES:    
 
  • Parking stands
   
       
SELECTION REMINDERS:    
       
1. Standard ratings for 15 / 25 kV  
L & Y Splice:
2. The standard splice is equipped with protective covers and a mounting
Voltage: to 25 kV,  bracket.
Impulse Voltage: to 125 kV BIL    
Corona Extinction: to 19 kV 3. Many combinations of 200/600
Standard ratings for 35 kV Y Splice: Amp junction bars are available. 
Voltage: 35 kV
Impulse Voltage: 150 kV BIL
Corona Extinction: 26 kV
 
ORDERING PROCEDURE:
 
1. Determine the following:  Example:
a.  Maximum voltage, kV.  25 kV(corona extinction=19 kV) 
b.  Current Rating, Amp. 4-200 Amp universal bushing wells
c. Number of positions required for
installation
required straight inline and 2-600A standard bushings required at 90 
d. Configuration of splice deg. 
    Catalog Number: JBL-4A/2B-19
2. Select catalog number of splice.
     
3. Provide the maximum voltage, kV and substitute its corresponding corona extinction value for x in the catalog number.  
 

Patton & Cooke by Cooper Power Systems
Contact your local Cooper Power System Representative for more details

Patton and Cooke Company